Measurement | Control | Dosing | Disinfection
Measurement | Control | Dosing | Disinfection

Peracetic Acid Sensor MPES7

Sensor for the measurement of peracetic acid C2H4O3up to 1% sulfur- and salpetre acid are tolerated.

Product description:

 

  • Measurement: Peracetic acid
  • Calibration: at the controller, via analytical determination by DPD-method
  • Interferences:

                        - ClO2 is registered with factor 1 of its measuring value

                        - H2O2 is registered with factor 0.005 of its measuring value - O3 is registered with factor 2500 of its measuring value,

  • pH range: 1 ... 6
  • Pressure range: 0 ... 1 bar, no pressure surges and/or fluctuations
  • Temperature range: 5 ... 45 °C,
  • Integrated automatic temperature compensation
  • Response time: T90 approx. 3 min,
  • Flow rate: approx. 30 l/h, low flow-dependence,
  • Shaft length: 175 mm, mA-Version 220 mm,
  • Material: PVC-U, stainless steel 1.4571 

 

 

Area of applications:

   

• Fresh water treatment, all types of water treatment

• Lead acids are tolerated

• Surfactants must not be existent

 

 

Scope of supply:

 

• MPES7: sensor, membrane cap, electrolyte

DOWNLOAD - 2016 MWC Peracetic Acid Sensor MP7 / Order- and Technical Data Sheet
20_MWC Peracetic acid Sensor MP7.pdf
PDF-Dokument [317.4 KB]
DOWNLOAD - 2016 MWC Peracetic Acid Sensor MP7 / Instruction Manual
110_MWC Instruction Manual MCD7_MP7_MOZ7[...]
PDF-Dokument [844.7 KB]
Druckversion Druckversion | Sitemap Diese Seite weiterempfehlen Diese Seite weiterempfehlen
© 2010 MWC Water Controls a brand of "Morguen Group" | Ravensburg / Germany | Istanbul / Turkey | Shanghai / China | Tel: +90 536 989 7618 | info@morwater.de |